GE IS200TDBTH6ACD工业自动化 控制模块 DCS PLC系统
is200tdbth6add系统功能
3.1监控告警
被监控设备的电源电路开关状态
被监控设备电源的工作状态(电压、电流、报警状态信息)
告警响应时间:≤30s
报警声音信号:可手动消除,当有报警信号再次输入时,可重新启动
报警灯信号:红色led指示灯亮
3.2故障告警
监视器与模块(电压/电流信号传感器)之间的连接线断开或短路
监控主电源欠压(≤80%主电源电压)或过压(≥110%主电源电压)
监视器与其分路电源之间的连接线断开或短路
当监视器出现上述故障时,可发出与监控报警信号明显不同的声光故障报警信号
故障告警响应时间:≤100秒
故障报警声音信号:手动消除,当有报警信号再次输入时,可重新启动
故障报警灯信号:黄色led灯常亮
故障发生时,不影响非故障环的正常工作
3.3控制输出
对单个或所有监控设备的报警继电器进行远程操作
监控报警控制输出:常开无源触点,容量:ac250v 3a或dc30v 3a
监视器控制输出:常开无源触点,容量:ac250v 3a或dc30v 3a
is200tdbth6acd System functions
3.1 Monitoring Alarm
Status of the power circuit switch of the monitored device
The working status of the power supply of the monitored equipment (voltage, current and alarm status information)
Alarm response time: ≤30s
Alarm sound signal: can be manually eliminated, when there is an alarm signal input again, can start again
Alarm light signal: red led indicator light on
3.2 Fault Alarm
The connection line between the monitor and the module (voltage/current signal sensor) is broken or short-circuited
Monitor main power undervoltage (≤80% main power supply voltage) or overvoltage (≥110% main power supply voltage)
The connection line between the monitor and its split power supply is broken or short-circuited
When the monitor has the above faults, it can send an audible and optical fault alarm signal that is obviously different from the monitoring alarm signal
Fault alarm response time: ≤100s
Fault alarm sound signal: manually eliminate, when there is an alarm signal input again, can start again
Fault alarm light signal: yellow led indicator is steady on
During the fault, the normal operation of the non-fault loop is not affected
3.3 Control Output
Remote operation of alarm relays for individual or all monitored devices
Monitor alarm control output: normally open passive contact, capacity: ac250v 3a or dc30v 3a
Monitor control output: normally open passive contact, capacity: ac250v 3a or dc30v 3a